Installation & Wiring

Power Wiring

Precautions:

Figure 2.3 Power wiring block diagram
Input power supply

Figure 2.4 Power terminal block descriptions

1 DC Bus Reactor would be used to assist in limiting harmonic distortion from the 161 to the line and reducing capacitive heating due to low impedance lines.

ATTENTION

• Ensure that the input voltage corresponds to the voltage indicated on the product nameplate.
• In normal operation apply the START/STOP commands via the control terminals or the control

panel and not by disconnecting and reapplying input power to the drive or motor contactor. If it
is necessary to use this method for starting and stopping, or if frequent cycling of power is
unavoidable, make certain it does not occur more than once every 5 minutes. Do not install any
capacitors or suppressors to the drive output terminals.

• Exercise particular caution if automatic restart is activated. To prevent injuries caused by

automatic restarting of the drive following a power failure, install a switching component at the input
that is deactivated in the event of a power failure and that may only be manually switched
on again on return of the power supply (e.g. contactor etc.).

• Suitable for use on a circuit capable of delivering not more than 5,000 rms symmetrical amperes,

240V maximum.

Terminal

Description

L1, L2, N/L3

Connection to incoming power. For single phase input applications, connect the AC input power to

input terminals L1 and N/L3

U/T1, V/T2, W/T3

Motor connections

-/+

DC Bus connection

+1

+

These terminals are connected by a jumper. For applications requiring a DC bus reactor, remove

the jumper prior to installing the third party device.
Protective earth ground connection

Disconnect

Device

Fuses

Optional

Filter

L1

Bulletin 161

L2

N/L3

U/T1

V/T2

W/T3

DC

Bus

+

+1

3

Motor

Optional
DC Bus Reactor

1

L1
AA01 - AA03 Power terminal block

L2 N/L3 U/T1 V/T2 W/T3

L1

All ratings except AA01 - AA03 Power terminal block

L2 N/L3 U/T1 V/T2 W/T3

*

*

*

+1

+

+1

(/)

+

*

Not Used