Attention, Control wiring, Requirements – Rockwell Automation 161 SERIES B FRN 2.001 User Manual

Page 13: Control terminal block wiring specifications

Advertising
background image

9

Installation & Wiring

Control Wiring

Requirements

Run all signal wiring in either a shielded cable or separate metal conduit.

Do not exceed control wiring length of 20 meters (65.6 feet).

Use Belden 8760 (or equivalent) –18 AWG (0.750mm

2

), twisted pair, shielded or 3 conductor.

Avoid crossing the power lines or motor lines with the control wires. If they must cross, ensure that they
cross at right (90

o

) angles.

If using transistor outputs 11 or 12, with an inductive load such as a relay, install a recovery diode parallel
to the relay as shown in Figure 2.6, to prevent damage to the output.

Control Terminal Block Wiring Specifications

Note: 0.75mm

2

(18 AWG) wire must be used for the alarm relay. Torque the mounting screw

to: 0.5-0.6 Nm (4.4-5.3 in lb).

Figure 2.6 Control Wiring Block Diagram

Figure 2.7 Control terminal block descriptions

Max/Min wire size mm

2

(AWG)

Max/Min Torque Nm (in lb)

0.750 – 0.14 (18-28)

0.25 - 0.2 (2.21 – 1.77)

ATTENTION

A hazard of electrical shock, death or equipment damage exists.

Control terminals are isolated but not tied to earth ground. If

terminal (L) on the control terminal block is not grounded,

exposed conductors, shields or metal conductors can be at

hazardous voltage levels.

Failure to observe this precaution could result in severe injury or

loss of life.

0-10V

1-2k Ohm

Pot.

4-20mA

Frequency

Reference

10V

P24

1

2

3

4

5

L

H

O

OI

L

Internal
Power

P24

1

24V

2

3

4

5

L

External
Power

IMPORTANT: Only one frequency
source may be connected at a time.
If more than one reference is
connected at the same time,
an undetermined frequency
reference will result.
To improve noise immunity, the
common (terminal L) must be
connected to ground terminal/
protective earth.

0-10V
PWM OutPut

230V AC

Fault Relay

FM

L

AL0

AL1

AL2

V

~

11

12

CM2

CM2

See Note 2

Parm
C01
C02
C03
C04
C05

Input

Terminal
1
2
3
4
5

Factory Default

Setting & Description

"U"

Default
22
20
21
18
13

1

"U" Default

Description
3 wire fwd/rev
3 wire run
3 wire stop
reset
USP

Parm
C01
C02
C03
C04
C05

Input

Terminal
1
2
3
4
5

Factory Default

Setting & Description

"K"

Default
0
1
2
3
13

"K" Default

Description
Run fwd
Run rev
Preset input 1 (CF1)
Preset input 2 (CF2)
USP

Notes: 1. Parameter C13 is NC. This input must be active

(jumpered) for the drive to run. See following pages
for description of these settings.

2. A contact closure on terminals 3 and P24 is required
for the controller to respond to a Start/Run command.

2