Parameters & Programming

30

1

U = 60 Hz default settings, K = 50 Hz default settings. Settable using

P

b85 – [Factory Default Select]

2

5hp (3.7 kW) ratings have a default value of 35%.

Parameter
Number

Parameter Name / Description

Min./Max
Range

Units

Factory

Defaults

Current Limit

U

1

K

1

b21

[Current Limit Select]
Selects the mode for current limit.
Settings:

00=Inactive

01=Active

02=Inactive in acceleration

00/02

Numeric

Value

01

01

b22

[Current Limit]
Sets the maximum output current allowed before
current limiting occurs. Value set in percent of drive
rated output current.

50/150% of
rated current

0.01 A

150% of

drive

rating

150% of

drive

rating

b23

[Current Limit Decel Time]
Sets the deceleration time when the current limiting
occurs.

0.3/30.0

0.1 second

1.0

1.0

Parameter Protection

U

1

K

1

b31

[Program Lock Select]
Sets the mode of program lock used.
Settings:

00=All parameters locked when digital
input setting 15 {SFT} active.

01=All parameters locked except PF01

– [Frequency Command] when
digital input setting 15 {SFT} active.

02=All parameters locked

03=All parameters locked except PF01

– [Frequency Command].

00/03

Numeric

Value

01

01

Current Feedback Tuning

U

1

K

1

b32

[Reactive Current Setting]
Use to improve accuracy by calibrating drive
motor combination. For improved accuracy,
adjust this value during no load operation until
Pd02 - [Output Current] matches actual motor
current.

0.00/100%

0.01A

40% of

drive

rating

2

40% of

drive

rating