23

Parameters & Programming

A03

[Base Frequency]
Set value to rated nameplate frequency of motor

50/360

1 Hz

60

50

A04

[Maximum Frequency]
Highest frequency the drive will output.

Note: If a maximum frequency less than

PA03 – [Base Frequency] is

needed, use

PA61 – [Upper Frequency Limit].

Refer to diagram in

PA03 – [Base Frequency].

50/360

1Hz

60

50

Analog input reference adjustment

U

1

K

1

A11

[Analog Frequency Minimum]
Sets the frequency that corresponds to a 0V or 4mA
analog signal.

0.0/360.0

0.1 Hz

0.0

0.0

A12

[Analog Frequency Maximum]
Sets the frequency that corresponds to a 10V or 20mA
analog signal. A value of 0.0 will disable this function.

Refer to diagram in

PA11 – [Analog Frequency Minimum].

0.0/360.0

0.1 Hz

0.0

0.0

A13

[Analog Input Minimum]
Sets the starting point (offset) for the analog input range.

Refer to diagram in

PA11 - [Analog Frequency Minimum]

0/99

1%

0

0

A14

[Analog Input Maximum]
The ending point (offset) for the analog input range.

Refer

to diagram in

PA11 - [Analog Frequency Minimum].

0/100

1%

100

100

A15

[Analog Start Select]
Sets the output frequency when frequency reference is
below value set in PA13 – [Analog Input Minimum].
Settings:

00 = PA11 - [Analog Frequency Minimum]

01 = 0 Hz

00/01

Numeric Value

01

01

A16

[Analog Filter Select]
Sets the level of the Analog input smoothing filter where:

1 = low. (Bandwidth = 200 Hz)

8 = high. (Bandwidth = 25 Hz)

1/8

Numeric Value

8

8

Parameter
Number

Parameter Name / Description

Min./Max
Range

Units

Factory

Defaults

Basic Functions

U

1

K

1

Voltage

100%

0

Start

Frequency

b82

Base

Frequency

A03

Maximum

Frequency

Frequency

Frequency

Frequency Limit
A61

Minimum
Frequency

A62

Hz

Command

Upper

A04

A12

A11

0V

10V

A13

A14

4mA

20mA

% Input

Scale

Frequency

A15=00

A15=01

A12

A11

0V

10V

A13

A14

4mA

20mA

% Input

Scale