25

Parameters & Programming

1

U = 60 Hz default settings, K = 50 Hz default settings. Settable using

P

b85 – [Factory Default Select]

Parameter
Number

Parameter Name / Description

Min./Max
Range

Units

Factory

Defaults

V/F Characteristics / Boost

U

1

K

1

A41

[Boost Select]
Used to select auto or manual boost
Settings:

00=Manual Boost
01=Auto Boost

00/01

Numeric

Value

00

00

A42

[Manual Boost Voltage]
Sets the boost level as a percent of PA82 - [Base
Voltage].

This Parameter

can be changed while motor is running.

0/99

Numeric

Value

25

11

A43

[Manual Boost Frequency]
Sets the boost frequency point as a percent of PA03 -
[Base Frequency].

Refer to diagram in

PA42 –

[Manual Boost Voltage]
This Parameter

can be changed while motor is running.

0.0/50.0%

0.1%

2.0

10.0

A44

[V/Hz Select]
Used to select the V/Hz mode.
Settings:

00=Constant Torque

01=Variable Torque

00/01

Numeric

Value

00

00

A45

[Maximum Voltage Gain]
Sets the voltage gain of the V/Hz characteristic.
Value is a percent of PA82 - [Base Voltage].

This Parameter

can be changed while motor is running.

50/100

1%

100

100

Voltage

100%

A42

A43

30Hz

60Hz

99 = 20%

of Base Voltage at 0Hz,
then linear scale down
e.g. 25 = 5%

~

~

1/2 Base

frequency

Base frequency

Frequency

Voltage

A44 = 00
Constant
Torque

A44 = 01
Variable
Torque

100%

0

Base frequency

frequency

Base frequency

frequency

100%

50%

A45

0