33

Parameters & Programming

C Group – Intelligent I/O and Communication Parameters

This parameter group is used to program the functions of the digital and analog I/O.

1

U = 60 Hz default settings, K = 50 Hz default settings. Settable using Pb85 – [Factory Default Select]

ATTENTION

All digital inputs respond to level sensitive commands.

Inputs do not require a voltage transition (cycle) after a fault condition is cleared, after input power cycling or after
programming the logic of the digital input.

All digital inputs can be programmed as NO or NC. HOWEVER, The START COMMAND SHOULD BE SET AS NO (ACTIVE
HIGH)
AND THE STOP COMMAND SHOULD BE SET AS NC (ACTIVE OPEN). If set opposite of this, an inadvertent start
or failure to stop could occur should a discrete connection be lost or control wire come loose. IF THE USER CHOOSES TO
DISREGARD THIS SAFETY PRACTICE – THE RISK ASSUMED BY THE USER CAN BE REDUCED BY ASSURING THAT
OTHER SAFEGUARDS ARE USED TO INSURE PROPER START AND STOP OPERATION. Depending on the application:
This may include appropriate emergency stops, redundant wiring, electronic guards and/or mechanical guards.
Failure to observe this precaution could result in severe bodily injury or loss of life.

Parameter
Number

Parameter Name / Description

Min./Max
Range

Units

Factory

Defaults

Digital Inputs 1 – 5

U

1

K

1

Parameter
C01

[Digital Inputs 1-5]
Used to program the function of digital inputs 1 – 5.

Settings:

00={FW} (Forward)
01={RV} (Reverse)
02={CF1} (Preset Frequency Input)
03={CF2} (Preset Frequency Input)
04={CF3} (Preset Frequency Input)
05={CF4} (Preset Frequency Input)
06={JG} (Jog)
09={2CH} (Accel/Decel 2 Select)
11={FRS} (Coast to Stop)
12={EXT} (External Trip)
13={USP} (Unintentional Start Protection)
15={SFT} (Program Lock)
16={AT} (4-20mA Select)
18={RS} (Reset)
19={PTC} (PTC Input) input C05 only
20={STA} (3 Wire Run)
21={STP} (3 Wire Stop)
22={F/R} (3 Wire Forward/Reverse)
27={UP} (Remote Control Up)
28={DWN} (Remote Control Down)
31={OPE} (Run/Stop Command Source Select)

Refer to Chapter 2 for setting descriptions of the “Programmable

Digital Input Functions” listed above.

00/31

Numeric Value

22

00

C02

20

01

C03

21

02

C04

18

03

C05

13

13

C11

[Digital Inputs 1-5 Logic]
Sets the digital inputs to be NO or NC contacts

Settings:

00=NO contact (active high)
01=NC contact (active open)

00/01

Numeric Value

00

00

C12

00

00

C13

01

00

C14

00

00

C15

01

01

Outputs 11, 12, FM, AL0-AL1

U

1

K

1

C21

[Digital Outputs 11-12] Sets the operation of the
digital outputs

Settings:

00={RUN} (Motor running above 0.5 Hz)

01={FA1} (At frequency and above 0.5 Hz)

02={FA2} (Above frequency)
03={OL} (Overload alarm)
04={OD} (PID deviation)

05={AL} (Fault)

Refer to control terminal table in Chapter 2 for setting descriptions

.

00/05

Numeric
Value

01

01

C22

00

00