31

Parameters & Programming

1

U = 60 Hz default settings, K = 50 Hz default settings. Settable using

P

b85 – [Factory Default Select]

Parameter
Number

Parameter Name / Description

Min./Max
Range

Units

Factory

Defaults

Initialization / Adjustment Function

U

1

K

1

b81

[Output FM Adjustment]
Sets the multiplier applied to output duty cycle for the
FM analog signal.

This Parameter

can be changed while motor is running.

0/255

N/A

80

80

b82

[Start Frequency]
Sets the frequency at which the drive will start.

Refer to diagram in

P

A03 – [Base Frequency]

0.5/9.9

0.1 Hz

0.5

0.5

b83

[PWM Frequency]
Carrier frequency for the PWM output waveform.
Output current must be derated by twenty percent
when set above 12 kHz.

0.5/16.0

0.1 kHz

5.0

5.0

b84

[Reset Functions]
Resets the factory defaults or clears fault history.
Settings:

00=Clear fault history
01=Reset defaults

Note: To activate this parameter, set the value and press the Enter
Key, then hold the SELect, Up, Down, and STOP Keys for 3
seconds, release only the STOP Key until display is blinking, then
release all of the keys.

Note: Defaults will reset to factory settings determined by Pb85 –
[Factory Defaults Select]

00/01

Numeric Value

01

00

b85

[Factory Default Select]
Determines the default settings of all parameters. The
drive will reset to these default values when a “reset
defaults” command is executed as described in Pb84,
setting 01 = reset defaults.
Settings: 06=K (50 Hz default settings)
07=U (60 Hz default settings)

Note: Parameter default values for settings 00 - 05 are not
published in this manual and are not recommended. If using these
default settings

Pb87 becomes active. Refer to the Attention

statement under

Pb87.

06/07

Numeric Value

07

06

b86

[Process Display Scale Factor]
Sets the frequency factor for Pd07 –[Process Display].
Also sets the multiplier that is applied to the output
frequency for the FM pulse signal.

This Parameter

can be changed while motor is running

0.1/99.9

N/A

30.0

1.0

b87

[STOP Key Select]
This parameter is not active when Pb85 is set to setting
06 or 07.

ATTENTION:

If

Pb85 settings 00 through 05, are activated,

this parameter will control the operation of the keypad STOP key. Setting
00 will enable the STOP key and 01 will disable the STOP key. Disabling
the STOP key is not recommended as it could result in personal injury, loss
of life or equipment damage.

00/01

Numeric

Value

00

00