Rockwell Automation 161 SERIES B FRN 2.001 User Manual

Page 33

Advertising
background image

29

Parameters & Programming

b Group – Advanced Control and Protection Parameters

1

U = 60 Hz default settings, K = 50 Hz default settings. Settable using

P

b85 – [Factory Default Select]

Parameter
Number

Parameter Name / Description

Min./Max
Range

Units

Factory

Defaults

Automatic Start After a Fault

U

1

K

1

b01

[Restart Mode Select]
Selects the restart mode for the drive
Settings:

00=Fault indication

01=0 Hz start

02=Synchronize.

03=Synchr. and stop

Note: If set to 01, 02 or 03 the drive will attempt to restart the
following number of times after the following events:
Overcurrent – 3 restarts
Overvoltage – 3 restarts
Undervoltage – 16 restarts (refer to

Pb03 – [Restart Time] for time

between restart attempts)

ATTENTION:

This parameter may only be used as

outlined in NFPA 79, “Under Voltage Protection.”
Equipment damage and/or personal injury may result if this
parameter is used in an inappropriate application.

00/03

Numeric Value

00

00

b02

[Power Loss Time]
If undervoltage exists longer than the
programmed time, the drive will fault even if Pb01 -
[Restart Mode Select] is active.

0.3/25.0

0.1

seconds

1.0

1.0

b03

[Restart Time]
Sets the time between restart attempts after an
undervoltage fault or the removal of a digital
input set to 11 {FRS}.

0.3/100.0

0.1

seconds

1.0

1.0

Parameter
Number

Parameter Name / Description

Min./Max
Range

Units

Factory

Defaults

Electronic Thermal Motor Protection

U

1

K

1

b12

[Motor Overload Current]
Set to motor nameplate full load amps.

5/120% of
rated
current

0.01A

115%

of drive

rating

115%

of drive

rating

b13

[Motor Overload Select]
Selects the characteristics of the electronic thermal
motor protection.
Settings:

00=Derating1
01=No Derating
02=Derating2

00/02

Numeric Value

01

01

Torque

100%

80%

60%

5Hz 20Hz

60Hz

Output frequency

b13 = 00

b13 = 01

b13 = 02

120Hz