Installation & Wiring

8

Power Terminal Block Wiring Specifications

Power Terminal Connection

IMPORTANT:

Bulletin 161 Drives feature an electronic overload protection to monitor the motor current. In the
case of multi-motor operation, thermal contacts or PTC resistors must be used for each motor.

In the case of motor lead lengths greater than 50 meters (165 feet), motor reactors should be used.

Branch Circuit Protection Devices

The following table shows the minimum recommended values for the branch circuit protection devices:

Input Power Conditioning

The drive is suitable for connection to input power within the rated voltage of the drive (see specifications).
The power factor of the input power supply must not exceed .99. Compensation systems must ensure that
over compensation does not occur at any time.
If the drive must be installed in any of the following conditions, an Input Line Reactor must be used:

Grounding

Ground the drive. Be sure to separate the drive’s grounding pole from those of other electrical machinery. If
multiple drives are used, make certain grounding connections do not create a loop as shown in Figure 2.5.

Figure 2.5 Suggested 161 Grounding

Model

Screw Size Max/Min Wire Size mm

2

(AWG)

Max/Min Torque Nm (lbin)

AA01-AA02

M3.5

2.1 – .75 (14-18)

0.9-0.8 (8.0-7.0)

AA03

M3.5

2.1 – 1.3 (14-16)

0.9-0.8 (8.0-7.0)

AA04, DA01

M4

5.3 – 1.3 (10-16)

1.3-1.2 (11.5-10.6)

AA05-AA10, DA02-DA03 M4

5.3 – 2.1 (10-14)

1.3-1.2 (11.5-10.6)

AA15

M4

5.3 – 3.3 (10-12)

1.3-1.2 (11.5-10.6)

Fuse Rating (Class CC, J)

Bulletin 140

Model

1 Ph

3 Ph

1 Ph

3 Ph

AA01

10

10

140M-D8N-C10

140M-D8N-B40

AA02-AA03

10

10

140M-D8N-C10

140M-D8N-B63

AA04-AA05

15

15

140M-D8N-C16

140M-D8N-C10

AA07

20

15

140M-D8N-C16

140M-D8N-C16

AA10

30

20

140M-D8N-C25

140M-D8N-C16

AA15

N/A

30

N/A

140M-D8N-C25

DA01

10

N/A

140M-D8N-C10

N/A

DA02

15

N/A

140M-D8N-C10

N/A

DA04

20

N/A

140M-D8N-C16

N/A

Input Power Condition

Corrective Action

Line has intermittent noise spikes in excess of 2000V

Install 3% impedance Input Line Reactor

If frequent voltage dips occur

Install 3% impedance Input Line Reactor

The drive is operated on a generator

Install 3% impedance Input Line Reactor

Line has power factor correction capacitors

Install 3% impedance Input Line Reactor

Several drives are linked via a short common power supply bus bar.

Install 3% impedance Input Line Reactor

ATTENTION

• The Bulletin 161 has a high leakage current and must be permanently (fixed) hard wired to ground.

Failure to observe this precaution could result in severe bodily injury or loss of life.