Mounting isolation switch handle module – Rockwell Automation 1503 OEM Starter Frame Components Installation Manual User Manual

Page 11

Advertising
background image

Component Installation 2-3

1503-IN050E-EN-P – June 2013

The handle is shipped in the OFF, or open, position. All

instructions assume the handle remains in the OFF

position during installation and adjustment procedures

unless otherwise stated.

Required Hardware:

• Six (6) ¼-20 x 0.5 in. (6.3 x 1.8 x 13mm Type B) self-tapping screws

• One (1) 5/16 in. (M8 x 1.25) grounding wire screw

Refer to the component layout shown in Figure 2.1 or 2.2 to determine the

mounting location and the location of the mounting holes for the isola-

tion switch handle module. Refer to Figure 2.3 for a detailed view of the

mounting holes.

1) Prepare a cut-out in the cabinet for the handle using the dimensions

shown in Figure 2.3.

2) Drill four (4) 0.281-in. (6.8 mm) clearance holes in the locations indi-

cated for the retaining screws.

9.53

[242]

1.00

[25]

1.06

[27]

0.53

[14]

4 X 0.219 (5.31)

Ø

MOUNTING HOLES

1.74

[44]

1.00

[25]

8.26

[210]

9.53

[242]

0.48

[12]

0.65

[17]

4 X Ø 0.281 [6.8]

CLEARANCE HOLES

Front Mounting Surface

Cutout Dimensions

Figure 2.3 – Handle Cut-out Dimensions

Front View

(Handle cut away

to show lower

mounting holes)

Front Mounting Surface

Cutout Dimensions

Mounting Isolation Switch

Handle Module

I M P O R T A N T

I M P O R T A N T

Isolation Switch Handle

(OFF Position)