Contactor interlock rod adjustment – Rockwell Automation 1503 OEM Starter Frame Components Installation Manual User Manual

Page 39

Advertising
background image

1503-IN050E-EN-P – June 2013

Adjustments

3-5

To avoid shock hazards, lock out incoming power (see

page 3-2) before working on the equipment. Verify with

a hot stick or appropriate voltage measuring device that

all circuits are voltage free. Failure to do so may result in

severe burns, injury or death.

1) Complete the Power Lock-out Procedure (see Page 3-2).
2) Open the medium voltage door. Use the Door Interlock Circumvention

procedure described on page 3-1 to move the isolation switch handle

halfway between the OFF and ON position (see Figure 3.6). Keep the

handle in this position until the adjustment procedure is completed.

3) With the contactor in the OFF position, insert a 0.050 in. (1.3 mm)

feeler gauge in the gap between the interlock lever and the isolation

switch operating lever. The gap must be between 0.045 in. to 0.060 in.

(1.1 mm to 1.5 mm).

4) To reduce the gap distance, follow steps 5-7.

To increase the gap distance follow steps 8-10.

Contactor Operating Lever

Contactor Interlock Rod

Stop Bracket

Interlock Lever

Isolation Switch Operating Lever

Isolation Switch Handle

at Halfway Position

Nylock Nut

Gap

(0.03 in. to 0.78 in.)

(1.00 mm to 2.0 mm)

Figure 3.6 – Isolation Switch Handle Adjustments

Contactor Interlock Rod

Adjustment

A T T E N T I O N

A T T E N T I O N