1503-IN050E-EN-P – June 2013

Adjustments

3-3

e) Electrically operate the contactor by pushing the START button

on the unit or at a remote location.

f) Disengage the contactor and move the control switch to the NOR-

MAL position. Disconnect the external power supply.

g) Complete the Power Lock-out procedure

4) Open the medium voltage door.

5) Visually inspect that the isolation switch blades fully engage the

grounding pins on the grounding bar. The isolation switch shutters

should be closed (see Figure 3.3).

Grounding Bar

Isolation Switch Blades must

fully engage Grounding Pins

of Grounding Bar

(Verify for each phase)

Isolation Switch Shutters

must be closed.

(Verify for each phase)

Figure 3.3 – Inspecting Isolation Switch in Open Position

6) Check the line and load sides of the contactor with a hot stick or appro-

priate voltage measuring device to verify that they are voltage free (see

Figure 3.4).

a) Check for line-side voltage at the top vacuum bottle terminals.

b) Check for load-side voltage at the bottom vacuum bottle terminals.