3-10

Adjustments

1503-IN050E-EN-P – June 2013

Isolation Switch Auxiliary

Contacts (cont.)

4) Adjust the cam on the shaft so that the gap from the cam follower to

the end of the cam groove is the width of the pin — 0.25 in. (6.35 mm).

5) Move the isolation switch handle to the OFF (open) position and check

that nothing prevents the cam from rotating with the shaft.

6) Tighten the bolt holding the cam to the shaft. Move the isolation switch

handle to the ON position and recheck the gap using the pin.

7) Verity that auxiliary contact ISa is open when the isolation switch is

open. Verify that ISa contact is closed when isolation switch is closed.

Adjusting the Normally Closed (ISb) Contacts

1) Move the isolation switch handle to the OFF (open) position.
2) Loosen the bolt holding the inside cam to the shaft. Do not loosen the

bolt entirely. The cam should not be able to rotate freely on the shaft.

3) Insert a 0.25 in. (6.35 mm) diameter pin into the cam groove between

the cam follower and the end of the cam groove.

4) Adjust the cam on the shaft so that the gap from the cam follower to

the end of the cam groove is the width of the pin — 0.25 in. (6.35 mm).

5) Move the isolation switch handle to the ON (closed) position and

check that nothing prevents the cam from rotating with the shaft.

6) Tighten the bolt that holds the cam to the shaft. Move the isolation

switch handle to the OFF position and recheck the gap using the pin.

7) Operate the handle several times, then recheck the 0.25 in. (6.35 mm)

clearance between the end of the cam groove and the follower pin for

both cams.

8) Verify that auxiliary contact ISb is closed when isolation switch is

open. Verify that ISb contact is open when isolation switch is closed.