Component Installation 2-17

1503-IN050E-EN-P – June 2013

7) Move the handle to the OFF position. Swing the door closed and

inspect the position of the Z-clip with respect to the handle pin.

8) Set the Z-clip so that it is just above the handle pin. Do not set the Z-clip

more than 0.125 in. (3 mm) above the pin. Tighten the screws.

9) Close the door and move the isolation switch handle to the ON posi-

tion. If the handle will not move to the ON position, the cover catch is

set too high and is not contacting the defeater lever. Open the door and

set the cover catch lower. Verify correct functioning.

10) Swing the door shut and move the isolation switch handle to the ON

position. Verify that the door interlock assembly is functioning properly.

The mechanical interlock is the primary safety mecha-

nism preventing access to the medium voltage power

cell. The mechanism also prevents opening or closing

the isolation switch under load (ie. it is a non-load-break

switch). A secondary electrical interlock is intended to

disengage the contactor in the event of a mechanical in-

terlock failure. See page 3-8 for additional information.

When properly connected, the isolation switch operating mechanism is

designed to provide the following safety features:
• Prevent the opening of any medium voltage door interlocked with the

mechanism while the handle is in the ON position and the unit is energized.

Prevent moving the handle to the ON position and energize the unit

while the medium voltage door is open.

Disengage the contactor from the RUN mode when the handle is

moved from the ON to OFF position.

Right Side View

Connection Point

(Clevis and Cotter Pin)

Isolation Switch

Operating Lever

Connecting Rod

Disconnect Lever

Figure 2.16 – Handle Mechanism Connection

I M P O R T A N T

I M P O R T A N T

Connecting Isolation Switch

to Isolation Switch Handle