Rockwell Automation 1503 OEM Starter Frame Components Installation Manual User Manual

Page 30

Advertising
background image

2-22

Component Installation

1503-IN050D-EN-P – June 2012

1) Use the supplied 5/16 in. hardware to mount the bus link or suitable

cable to the trailer fuse block (see Figure 2.20). Torque the bolts to the

specifi cations shown on page 1-4.

The trailer fuse block is equipped with 5/16-18 nuts. The

supplied hardware, or equivalent, must be used to avoid

damaging the thread in the nuts.

Trailer Fuse

Trailer Fuse Block

Attachment Point

Contactor

Attachment Point

(Line Side)

Figure 2.20 – Linking Trailer Fuse Block to Contactor (Clip-on Power Fuses)

2) Attach the bus links, or suitable cable, to the line side of the contactor

(upper terminals) using 3/8 in. (M10) hardware (see Figure 2.20).

Torque the bolts according to the requirments shown on page 1-4.

Maintain at least 3 in. (76 mm) clearance between power

phase connections. Insuffi cient distance could cause

equipment damaging power faults in the unit.

A T T E N T I O N

A T T E N T I O N

I M P O R T A N T

I M P O R T A N T

Electrical Connection From

Contactor to Trailer Fuse Block

(Clip-on Fuses)

(cont.)

Advertising