3-8

Adjustments

1503-IN050E-EN-P – June 2013

Isolation Switch (Cut-away view from right side)

Ground Bar

Incoming Line Stab

Isolation Switch Blade

Auxiliary Contact

Maximum Gap 0.06 in. (1.5 mm) between Ground Bar

and Isolation Switch Blade in open position

Figure 3.9 – Isolation Switch Ground Adjustment

Isolation Switch Auxiliary

The auxiliary contacts are mounted on the left side of the isolation switch,

Contacts

slightly below the cams on the isolation switch shaft.

Normally open contacts (Isolation Switch a Contacts - ISa) are on the

outside of the isolation switch housing, and normally closed contacts

(Isolation Switch b Contacts - ISb) are on the inside of the housing.

Isb Auxiliary Contacts (N.C.)

Isa Auxiliary Contacts (N.O.)

Figure 3.10 – Location of Isa and Isb Auxiliary Contacts

Isolation Switch Ground

Adjustment (cont.)