1503-IN050D-EN-P – June 2012

Adjustments

3-9

ISa and ISb contacts are exactly the same (700 CPM). The cam controls the

normally open or normally closed status of the contacts.

Refer to Figures 2.10 to 2.13 for wiring diagrams.

Important: The Isolation Switch Ground Adjustment procedure (page 3-7)

must be completed before adjusting the auxiliary contacts to ensure proper

synchronization of the assembly.

Adjusting the Normally Open (ISa) Contacts

To avoid shock hazards, lock out incoming power

before working on the equipment. Verify with a hot stick

appropriate voltage measuring device that all circuits are

voltage free. Failure to do so may result in severe burns,

injury or death.

1) Move the isolation switch handle to the ON (closed) position.

2) Loosen the bolt holding the outside cam to the shaft. Do not loosen the

bolt entirely. The cam should not be able to rotate freely on the shaft.

3) Insert a 0.25 in. (6.35 mm) diameter pin into the cam groove between

the cam follower and the end of the cam groove.

CATA

LO

G NO

.

700-CPM

SER. A

20

AMP

Cam

Cam Follower

Auxiliary Contact

Gap

0.25 in.

(6.35 mm)

Left Side View

Figure 3.11 – Adjusting Auxiliary Contacts (Isa Auxiliary Contact Shown)

A T T E N T I O N

A T T E N T I O N