Rockwell Automation 1503 OEM Starter Frame Components Installation Manual User Manual

Page 8

Advertising
background image

1-4

OEM Starter Frame Installation

1503-IN050E-EN-P – June 2013

Installation (Cont.)

IntelliVAC

Refer to Publication 1503-UM051_-EN-P or 1503-UM052_-EN-P for

IntelliVAC mounting instructions. Note that a suitable wire harness is

required (1503-WHxxx) to connect IntelliVAC to the vacuum contactor.
Refer to “IntelliVAC”, page 2-10 for more information and wiring diagrams.

Torque Requirements

Use the specifi ed torque values for all hardware whenever performing

maintenance or attaching components.

1/4 in. (M6) hardware

6 ft•lb (8 N•m)

5/16 in. (M8) hardware

12 ft•lb (15 N•m)

3/8 in. (M10) hardware

20 ft•lb (27 N•m)

1/2 in. (M12) hardware

48 ft•lb (65 N•m)

Fuses

Refer to the motor nameplate for the information necessary to determine

correct power fuse size. See page 2-7 for recommended power fuses.

Only qualifi ed personnel should select the fuse type and

rating. Failure to select the correct fuses may result in

injury to personnel and/or damage to equipment.

1) Install clip-on or bolt-on power fuses into the isolation switch fuse clips.
2) If control power is supplied by control power transformer within the

unit, fuses may be installed in the control circuit transformer primary

fuse clips at the top of the contactor (see page 2-24 for details).

Line and Load Connections

See Incoming Line Connections (page 2-24) and Load Connections (page

2-24).

Commissioning

See Commissioning, Chapter 4.

A T T E N T I O N

A T T E N T I O N

Advertising