Adjustments

3-11

Adjusting the ‘Change of State Point’

This procedure sets the secondary electrical interlock.

When properly adjusted, the electrical interlock is

designed to open the control circuit power connections

before the isolation switch opens when the handle is

moved to the OFF position.

1) Once the auxiliaries have been adjusted, move the isolation switch

handle to the ON position.

2) Connect a conductivity measuring device across the closed auxiliary

contacts.

3) Slowly move the isolation switch handle towards the OFF position and

observe the point at which the movable isolation switch blades separate

from the incoming line stabs. The auxiliary contacts must change state

from the closed to open position before the isolation switch blades lose

contact with the incoming line stabs. This prevents the isolation switch

from being opened while the unit is energized and under load condi-

tions.

The auxiliary contacts must be properly adjusted to

avoid opening the isolation switch under load conditions.

Improper adjustment may result in damage to the

equipment and/or severe burns, injury or death to

personnel.

4) If the auxiliaries do not change state before the isolation switch opens,

adjust the threaded connecting rod as described in the Isolation Switch

Adjustment procedure (see page 3-7).