Powermonitor 3000 Master Module 15

Publication 1404-IN007F-EN-P - November 2009

Master Module Spacing

Powermonitor 3000

Powermonitor 3000

Powermonitor 3000

Powermonitor 3000

50.8

(2.00)

50.8

(2.00)

50.8 (2.00)

Minimum

50.8 (2.00)

Minimum

101.6 (4.00)

101.6 (4.00)

215.9 (8.50)

215.9 (8.50)

General Notes:

• Recommended spacing provides reasonable wiring clearance and ventilation.
• Maintain approximately 102 mm (4.00 in.) clearance between master modules and other

electrical equipment.

• Do not block cooling vents. Wiring and other obstructions must be 50 mm (2.00 in.) minimum

from top and bottom of unit.

• Mount with ventilation opening in top and bottom to provide optimum free convection cooling.
• Refer to

Specifications

for ambient temperature requirements.

All dimensions are in mm (in.).