Master module spacing – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 Master Module Installation Instructions User Manual
Page 15
![background image](/manuals/579064/15/background.png)
Powermonitor 3000 Master Module 15
Publication 1404-IN007F-EN-P - November 2009
Master Module Spacing
Powermonitor 3000
Powermonitor 3000
Powermonitor 3000
Powermonitor 3000
50.8
(2.00)
50.8
(2.00)
50.8 (2.00)
Minimum
50.8 (2.00)
Minimum
101.6 (4.00)
101.6 (4.00)
215.9 (8.50)
215.9 (8.50)
General Notes:
• Recommended spacing provides reasonable wiring clearance and ventilation.
• Maintain approximately 102 mm (4.00 in.) clearance between master modules and other
electrical equipment.
• Do not block cooling vents. Wiring and other obstructions must be 50 mm (2.00 in.) minimum
from top and bottom of unit.
• Mount with ventilation opening in top and bottom to provide optimum free convection cooling.
• Refer to
for ambient temperature requirements.
All dimensions are in mm (in.).