Powermonitor 3000 Master Module 35

Publication 1404-IN007F-EN-P - November 2009

All Status Inputs are common to an internal 24V DC source on the SCOM terminal. Status
input terminals S1 and S2 are positive polarity and SCOM is negative polarity.

For optimal EMC performance, we recommend wiring the status inputs by using shielded
cable, Belden 8771 or equivalent, with the cable shield grounded at both ends where possible.

Status Input Connections

Applied resistance versus status state

• Condition 1 is 3.5 kW or less = ON
• Condition 2 is 5.5 kW or greater = Off

Isolation Voltage is 500V status input to case and 500V status input to internal digital
circuitry.

Relay and KYZ Outputs

Control Relay Connections on

page 36

shows the Form C relay output connections and an

example of customer wiring to a supply voltage and two loads. Terminal R11 is the common
connection, R14 is the normally-open connection, and R12 is the normally-closed
connection. You must supply the wetting voltage and overcurrent protection for the circuit
connected to the relay output.

Refer to Specifications on

page 56

for further information.

TIP

Status Input S2 can be configured for external demand pulse input. See the
Powermonitor 3000 User Manual, publication

1404-UM001

, for more information.

Powermonitor 3000

Master Module

-

+

R14

R14

R11

R12

N/C

N/C

I1-

I1+

I2-

I2+

I3-

I3+

I4-

I4+

Y

K

Z

R14

R11 R12

Y

K

Z

L1
(+)

L2
(-)

GRD

V1

S1

S2

SCOM

V2

V3

N

DISPLAY
MODULE

SHLD

RS-485

N.O.

Contact

N.O.

Contact

Advertising