Control power, Status inputs – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 Master Module Installation Instructions User Manual

Page 34

Advertising
background image

34 Powermonitor 3000 Master Module

Publication 1404-IN007F-EN-P - November 2009

Control Power

The power monitor draws a nominal 15VA control power. Catalog numbers
1404-M

xxxA-xxx require nominal control power of 120…240V AC or

125…250V DC. The power supply is self-scaling. Catalog numbers 1404-M

xxxB-xxx require

nominal control power of 24V DC.

Refer to Specifications on

page 56

for acceptable control-voltage ranges and wiring

termination information.

We strongly recommend that you use a separate source of control power from the power
system being monitored. For applications where power system information is critical,
consider the use of a user-supplied uninterruptible power supply so that the power monitor
continues to operate during power system events such as significant sags, swells, and transient
disturbances.

You are required to connect your power-monitor control power through user-supplied
disconnecting means and overcurrent protection. We recommend a 1 A slow-blow fuse.

Status Inputs

ATTENTION

Do not apply an external voltage to a Status Input. These inputs have an internal source
and are intended for dry contact input only. Applying a voltage may damage the
associated input or internal power supply.

L1

N/L2

Local

Frame

Ground

Powermonitor 3000

Master Module

R14

R11

R12

N/C

N/C

I1-

I1+

I2-

I2+

I3-

I3+

I4-

I4+

Y

K

Z

R14

R11 R12

Y

K

Z

L1
(+)

L2
(-)

GRD

V1

S1

S2

SCOM

V2

V3

N

DISPLAY
MODULE

SHLD

RS-485

Advertising