The shorting terminal block should be located adjacent to the Powermonitor 3000 master

module so that it is readily accessible should service be needed. Use 2.5 mm

2

(14 AWG) wire

for the short run between the power monitor and the shorting terminal block. Use wiring of 4

mm

2

(12 AWG) or larger between the shorting terminal block and the CT so that the

additional load of the wiring does not overload the CT and reduce its accuracy.

Do not install fuses or other overcurrent protection in the secondary circuit of a CT.

Refer to System Accuracy Considerations on

page 16

for guidelines on PT and CT selection.

Refer to Specifications on

page 56

for information on voltage isolation levels and wire

termination recommendations.

The wiring diagrams depict wiring methods for a variety of power system configurations. You
need to configure your power monitor to match the power system configuration for correct
operation.

Refer to the Powermonitor 3000 Unit User Manual, publication

1404-UM001

, for detailed

instructions on unit configuration.

IMPORTANT

You may install either two or three CTs for any of the Delta or Open Delta wiring or
voltage modes.

Refer to the wiring diagrams on pages

28

,

30

, and

33

for wiring of a two CT configuration.

Whether there are two or three CTs in a circuit does not affect the voltage wiring.

Refer to the Powermonitor 3000 Unit User Manual, publication

1404-UM001

.