50 Powermonitor 3000 Master Module

Publication 1404-IN007F-EN-P - November 2009

DeviceNet Status Indicators

EtherNet/IP Status Indicators

DeviceNet Optional Communication (catalog numbers ending in -DNT)

Indicator

Status

Description

F1

Off

Not used.

F2

Off

Not used.

Network Status

Off

Power is off or the power monitor is not online.

Flashing green

Network status is OK, no connections established.

Steady green

Network status is OK, connections established.

Flashing red

Recoverable communication failure; port is restarting.

Steady red

Nonrecoverable communication error; check wiring and
configuration parameters.

EtherNet/IP Optional Communication (catalog numbers ending in -ENT)

Indicator

Status

Description

LNK

Off

No valid physical EtherNet connection.

Steady green

Valid physical EtherNet connection.

ACT

Strobing or solid yellow

Power monitor transmitting onto the EtherNet/IP network.

F1

Off

Not used.

Powermonitor 3000

F1

F2

NETWORK
STATUS

F1

LNK

ACT

F2

NETWORK
STATUS

Powermonitor 3000