Rs-485 connections – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 Master Module Installation Instructions User Manual

Page 38

Advertising
background image

38 Powermonitor 3000 Master Module

Publication 1404-IN007F-EN-P - November 2009

RS-485 Connections

Shield Connection

(See Note 4)

IBM Compatible

Personal Computer

Or

PLC Processor

Or

SLC Processor

Or

ControlLogix Processor

Notes:
1)

2)

3)

4)

Powermonitor 3000 Device #1

Powermonitor 3000 Device #2

Powermonitor 3000 Device #3 (Last)

RS-485

RS-485

RS-485

External

RS-232C to RS-485

Converter

(See Note 3)

150

Ω

Terminating

Resistor

(See Note 2)

150

Ω

Terminating

Resistor

(See Note 2)

SHLD

SHLD

_

+

SHLD

_

+

SHLD

_

+

A

B

Three-device network shown. Up to 31 DF1
Slave Devices can be connected to a
DF1 Master without the use of a repeater.
Terminating resistors may be required for
networks with long distances or high noise
environments. Consult the RS-232 to RS-485
converter manufacturer for more informaiton.
Examples:
B&B Electronics
Part Number 485SD9TB (DB9)
Allen-Bradley Cat. No. 1761-NET-AIC
Shields should be connected at
one end only to avoid ground loops.