Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 Master Module Installation Instructions User Manual
Page 41

Powermonitor 3000 Master Module 41
Publication 1404-IN007F-EN-P - November 2009
Configuration options for optional remote I/O communication include the logical rack
address and module group (the power monitor is always one-quarter rack), and data rate.
Defaults are rack 1, group 0, 57.6 Kbps.
Refer to the Powermonitor 3000 Unit User Manual, publication
.
Refer to the note at the beginning of Communication Wiring on
Connecting Powermonitor 3000 Unit to Remote I/O Scanner
2
SHLD
1
2
SHLD
1
2
SHLD
1
2
SHLD
1
82
Ω
Terminating
Resistor
(See Note 2)
82
Ω
Terminating
Resistor
(See Note 2)
Blue
Shield
Clear
IBM Compatible
Personal Computer
With R I/O
Interface Card
Or
PLC Processor/
PLC R I/O Scanner
Or
Or
SLC R I/O Scanner
ControlLogix R I/O Scanner
Notes:
1) Three-device network portrayed.
Up to 32 slave devices can
be connected per master
R I/O channel.
2) Terminating Resistors
must be connected
to each end of the
R I/O network. Omit the
terminating
resistors
if the devices already
are equipped with internal
terminating
resistors.
R I/O
Powermonitor 3000 Device #3 (Last)
R I/O
Powermonitor 3000 Device #2
R I/O
Powermonitor 3000 Device #1