Powermonitor 3000 Master Module 41

Publication 1404-IN007F-EN-P - November 2009

Configuration options for optional remote I/O communication include the logical rack
address and module group (the power monitor is always one-quarter rack), and data rate.
Defaults are rack 1, group 0, 57.6 Kbps.

Refer to the Powermonitor 3000 Unit User Manual, publication

1404-UM001

.

Refer to the note at the beginning of Communication Wiring on

page 36

.

Connecting Powermonitor 3000 Unit to Remote I/O Scanner

2

SHLD

1

2

SHLD

1

2

SHLD

1

2

SHLD

1

82

Ω

Terminating

Resistor

(See Note 2)

82

Ω

Terminating

Resistor

(See Note 2)

Blue
Shield

Clear

IBM Compatible

Personal Computer

With R I/O

Interface Card

Or

PLC Processor/

PLC R I/O Scanner

Or

Or

SLC R I/O Scanner

ControlLogix R I/O Scanner

Notes:
1) Three-device network portrayed.
Up to 32 slave devices can
be connected per master
R I/O channel.
2) Terminating Resistors
must be connected
to each end of the
R I/O network. Omit the
terminating

resistors

if the devices already
are equipped with internal
terminating

resistors.

R I/O

Powermonitor 3000 Device #3 (Last)

R I/O

Powermonitor 3000 Device #2

R I/O

Powermonitor 3000 Device #1