Output Configuration Group (cont.)

[Analog Out Sel]

Parameter # 25

Factory Default “Frequency”

[Analog Out Sel]

Parameter Type Read & Write

This parameter selects the value to which the 0-10V DC

g u pu

T 2

er

s pr p r

Units None

Setting ‘‘Frequency”

0 to [Maximum Freq]

This parameter selects the value to which the 0-10V DC
analog output at TB2-5 terminal is proportional.

‘‘Current”

0 to 200% of Rated Drive Output Current)

g u pu

T 2

er

s pr p r

‘‘Bus Volts”

0 to Maximum Bus Voltage– 410V/230V Drives

815V/460V Drives

‘‘Power”

0 to 200% of Drive Rated OutputPower

[Above Freq Val]

Parameter # 77

Factory Default 0 Hz

[Above Freq Val]

Parameter Type Read & Write

Minimum 0 Hz

This parameter is used when [Output 1 Config] or
[Output 2 Config] is set to ‘‘Above Freq” to indicate when
the drive is operating above the specified frequency
setting.

Units Hertz

Maximum 400 Hz

IMPORTANT: This parameter can not be pro-
grammed while the drive is running.

[Above Curr Val]

Parameter # 142

Factory Default 0 % of Drive Rated Current ➀

[Above Curr Val]

Parameter Type Read & Write

Minimum 0 % of Drive Rated Current ➀

This parameter is used when [Output 1 Config] or
[Output 2 Config] is set to ‘‘Above Curr” to indicate when
the drive output current exceeds this value.

Units 1%

Maximum 150% of Drive Rated Current ➀

The drive rated output current is based on three phase input ratings. See page 5-13
for Single Phase Input Rating instructions.