Set up group (cont.) – Rockwell Automation 1305 AC Drive, Firmware 1.01-3.00 User Manual User Manual
Page 78

Chapter 5 – Programming
5-10
Set Up Group (cont.)
[Maximum Voltage]
Parameter # 20
Factory Default Max. Drive Rated Volts
[Maximum Voltage]
Parameter Type Read & Write
Minimum 25% of Max. Drive Rated Voltage
This parameter sets the highest voltage the drive will
output. IMPORTANT: [Maximum Voltage] must be greater
than or equal to [Base Voltage].
Units 1 Volt
Maximum 100% of Max. Drive Rated Volts
[Minimum Freq]
Parameter # 16
Factory Default 0 Hz
[Minimum Freq]
Parameter Type Read & Write
Minimum 0 Hz
This parameter sets the lowest frequency the drive will
output. IMPORTANT: All analog inputs to the drive
(4-20mA, 0-10V, Remote Pot) are scaled for the range
[Minimum Freq] to [Maximum Freq].
Units 1 Hz
Maximum 120 Hz
IMPORTANT: This parameter can not be pro-
grammed while the drive is running.
[Maximum Freq]
Parameter # 19
Factory Default 60 Hz
[Maximum Freq]
Parameter Type Read & Write
Minimum 40 Hz
This parameter sets the highest frequency the drive will
output. IMPORTANT: All analog inputs to the drive
(4-20mA, 0-10V, Remote Pot) are scaled for the range
[Minimum Freq] to [Maximum Freq].
Units 1 Hz
Maximum 400 Hz
IMPORTANT: This parameter can not be pro-
grammed while the drive is running.