Chapter 5 – Programming

5-10

Set Up Group (cont.)

[Maximum Voltage]

Parameter # 20

Factory Default Max. Drive Rated Volts

[Maximum Voltage]

Parameter Type Read & Write

Minimum 25% of Max. Drive Rated Voltage

This parameter sets the highest voltage the drive will
output. IMPORTANT: [Maximum Voltage] must be greater
than or equal to [Base Voltage].

Units 1 Volt

Maximum 100% of Max. Drive Rated Volts

[Minimum Freq]

Parameter # 16

Factory Default 0 Hz

[Minimum Freq]

Parameter Type Read & Write

Minimum 0 Hz

This parameter sets the lowest frequency the drive will
output. IMPORTANT: All analog inputs to the drive
(4-20mA, 0-10V, Remote Pot) are scaled for the range
[Minimum Freq] to [Maximum Freq].

Units 1 Hz

Maximum 120 Hz

IMPORTANT: This parameter can not be pro-
grammed while the drive is running.

[Maximum Freq]

Parameter # 19

Factory Default 60 Hz

[Maximum Freq]

Parameter Type Read & Write

Minimum 40 Hz

This parameter sets the highest frequency the drive will
output. IMPORTANT: All analog inputs to the drive
(4-20mA, 0-10V, Remote Pot) are scaled for the range
[Minimum Freq] to [Maximum Freq].

Units 1 Hz

Maximum 400 Hz

IMPORTANT: This parameter can not be pro-
grammed while the drive is running.