Appendix a – Rockwell Automation 1305 AC Drive, Firmware 1.01-3.00 User Manual User Manual

Page 134

Advertising
background image

Appendix A –

Block Diagram and Specifications

A-2

Table A.1 Specifications

Drive

Bulletin 1305 Drive Rated 200-230 V AC

Bulletin 1305 Drives Rated 380-460 V AC

r e

-AA02A

-AA03A

-AA04A

-AA08A

-AA12A

-BA01A

-BA02A

-BA03A

-BA04A

-BA06A

-BA09A

OUTPUT RATINGS

3 Phase Motor Rating
kW (HP)

0.37

(1/2)

0.55

(3/4)

0.75

(1)

1.5

(2)

2.2

(3)

0.37

(1/2)

0.55

(3/4)

0.75

(1)

1.5

(2)

2.2

(3)

4.0

(5)

Output Current (A) ➀

2.3

3.0

4.5

8.0

12.0 ➁

1.3

1.6

2.3

4.0

6.0 ➂

9.0 ➃

Output Voltage

Adjustable from 0 V to Input Voltage

Output Frequency (Hz)

0 to 400Hz Programmable

INPUT RATINGS

Input Voltage &
Frequency

200/230V Three Phase, 50/60 Hz

380/460V Three Phase, 50/60 Hz

Operational Range (V)

180-265V, 47-63 Hz

340V-500V, 47-63 Hz

Input kVA

0.9

1.3

1.7

3.1

4.6

0.9

1.3

1.7

3.1

4.6

7.0

Power Factor
(Displacement)

0.8 (Lagging)

Efficiency (%)

97.5 % (Typical)

Power Dissipation (W)

27

34

46

76

108

21

27

34

52

73

107

If the [PWM Frequency] is set above 4kHz, the output current rating must be derated per the chart on page 5-18.

Output current value listed for 200V input voltage. At 230V input voltage, output current is 9.6A for 3 phase.

Output current value listed for 380V input voltage. At 415V input voltage, output current is 5.3A. At 460V input voltage, output current is 4.8A.

Output current value listed for 380V input voltage. At 415V input voltage, output current is 8.4A. At 460V input voltage, output current is 7.6A.

Advertising