Chapter 5 – Programming
5-14
This group contains parameters that are required to setup advanced functions of the drive such as custom
Volts per Hertz settings and dynamic braking.
Advanced Setup
[Minimum Freq]
Parameter # 16
Factory Default 0 Hz
[Minimum Freq]
Parameter Type Read & Write
Minimum 0 Hz
This parameter sets the lowest frequency the drive will
output. IMPORTANT: All analog inputs to the drive
(4-20mA, 0-10V, Remote Pot) are scaled for the range
[Minimum Freq] to [Maximum Freq].
Units 1 Hz
Maximum 120 Hz
IMPORTANT: This parameter can not be pro-
grammed while the drive is running.
[Maximum Freq]
Parameter # 19
Factory Default 60 Hz
[Maximum Freq]
Parameter Type Read & Write
Minimum 40 Hz
This parameter sets the highest frequency the drive will
output. IMPORTANT: All analog inputs to the drive
(4-20mA, 0-10V, Remote Pot) are scaled for the range
[Minimum Freq] to [Maximum Freq]
Units 1 Hz
Maximum 400 Hz
IMPORTANT: This parameter can not be pro-
grammed while the drive is running.
[Base Frequency]
Parameter # 17
Factory Default 60 Hz
[Base Frequency]
Parameter Type Read & Write
Minimum 40 Hz
This value should be set to the motor nameplate Rated
Frequency.
Units 1 Hz
Maximum 400 Hz
Units 1 Hz
Maximum 400 Hz