Process display – Rockwell Automation 1305 AC Drive, Firmware 1.01-3.00 User Manual User Manual
Page 119

Chapter 5 – Programming
5-51
This group contains parameters that can be used to display a drive parameter in ‘‘User Units.”
Process Display
[Process Par]
Parameter # 127
Factory Default 1
[Process Par]
Parameter Type Read & Write
Minimum 1
This parameter should be set to the number of the
parameter whose scaled value will be displayed on
Line 1 of the HIM Display Panel when in process mode.
Units Numeric
Maximum Max. Parameter Number
[Process Scale]
Parameter # 128
Factory Default +1.00
[Process Scale]
Parameter Type Read & Write
Minimum –327.68
This value sets the scaling multiplier for [Process Par].
The displayed value will be:
[Process Par] actual value
[Process Scale] value
Displayed Value ➀
Units Numeric
Maximum +327.67
[Process Txt 1-8]
Parameter #(s) 129-136
Factory Default ‘‘?’’
[Process Txt 1-8]
Parameter Type Read & Write
These parameters set the ‘‘User Units” description for
the value determined by [Process Par] and [Process
Scale]. This text is displayed on Line 1 of the HIM.
Units ASCII Text
Character
➀
The maximum value that can be displayed is 99,999.99. If this value is exceeded a
character string of asterisks (
*******
) will appear on the display.