Feature select group (cont.) – Rockwell Automation 1305 AC Drive, Firmware 1.01-3.00 User Manual User Manual
Page 99

Chapter 5 – Programming
5-31
Feature Select Group (cont.)
[S Curve Time]
Parameter # 56
Factory Default 0.0 Sec
[S Curve Time]
Parameter Type Read & Write
Minimum 0.0 Sec
This parameter enables an adjustable shape S-Curve
accel/decel time. IMPORTANT: [S-Curve Time] must be
set to a value less than or equal to the Accel & Decel
times.
Units 0.1 Second
Maximum 300.0 Sec
a 1/2 '
S-Curve
Time
a 1/2 '
S-Curve
Time
a Decel Time '
1 or 2
a Accel Time '
1 or 2
Figure 5.17 S-Curve Time
Enabled
Disabled
a1/2 '
S-Curve
Time
[S-Curve Enable] must be ‘‘enabled” for this
parameter to be active. The [S-Curve Time]
setting is added to the active accel/decel times
to form an adjustable S-Curve.
IMPORTANT: If [Stop Select] is set to “S
Curve” then the decel time will be double the
active decel setting when a stop command is
provided.
a1/2 '
S-Curve
Time
[Language]
Parameter # 47
Factory Default ‘‘English”
[Language]
Parameter Type Read & Write
This parameter selects between English and the alternate
second language that can be displayed on the HIM.
Units None
Settings ‘‘English” or
“French”
“Italian”
“Japanese”
“Spanish”
“German”