Appendix b – Rockwell Automation 1305 AC Drive, Firmware 1.01-3.00 User Manual User Manual
Page 144

Appendix B –
Serial Communications
B-6
Table B.4 Parameter Grouping/User Settings (cont.)
Group
Parameter Name
Param-
eter #
Display
Units
Drive Units
Scale Factor ➁
Min
Max
Factory Setting
User‘s
Setting
Input Mode
21
Text ➀
1
––
––
Three Wire
Freq Select 1
5
Text ➀
1
––
––
Adapter 1
p
Accel Time 1
7
Seconds
10
0.0
3600.0
10.0
et U
p
Decel Time 1
8
Seconds
10
0.0
3600.0
10.0
Set
Base Frequency
17
Hz
1
40
400
60
S
Base Voltage
18
Volts
1
25% of DRV Drive Rated Volts
Drive Rated Volts
Maximum Voltage
20
Volts
1
25% of DRV Drive Rated Volts
Drive Rated Volts
Minimum Freq
16
Hz
1
0
120
0
Maximum Freq
19
Hz
1
40
400
60
Stop Select
10
Text ➀
1
––
––
Ramp
Current Limit
36
%
1
20% of
DRC
150% of Drive Rated Current (DRC)
150% of DRC
Overload Mode
37
Text ➀
1
––
––
No Derating
Overload Current
38
Amps
100 = DRC
20% of
DRC
115% of Drive Rated Current (DRC)
115% of DRC
Sec Curr Limit
141
%
1
0
150% of Drive Rated Current (DRC)
0
➀ Refer to Table B.5 on pages B-13, B-14 and B-15 for the numerical equivalent of the text descriptions. ➁ Refer to page B-2.