Chapter 5 – Programming

5-23

This group of parameters allows the user to program the frequency source, frequency settings, accel/decel
times and skip frequencies of the drive.

Frequency

Set

[Freq Select 1]

Parameter # 5

Factory Default “Adapter 1”

[Freq Select 1]

Parameter Type Read & Write

This parameter is the factory default parameter for
selecting the frequency source that will supply the [Freq
Command]
to the drive. [Freq Select 2] or [Preset Freq
1-7]
can be selected in place of this parameter with proper
terminal block inputs. Refer to charts on Pages 5-26 and
5-27.

Units None

Settings ‘‘Remote Pot”

‘‘0-10 Volt”
‘‘4-20 mA”
‘‘MOP”
‘‘Adapter 1”
‘‘Adapter 2”
‘‘Adapter 3”
‘‘Adapter 4”
‘‘Adapter 5”
‘‘Adapter 6”

‘‘Preset 1”
‘‘Preset 2”
‘‘Preset 3”
‘‘Preset 4”
‘‘Preset 5’’
‘‘Preset 6”
‘‘Preset 7”

[Freq Select 2]

Parameter # 6

Factory Default ‘‘Remote Pot”

[Freq Select 2]

Parameter Type Read & Write

This parameter controls which of the frequency sources is
currently supplying the [Freq Command] to the drive
unless [Freq Select 1] or [Preset Freq 1-7] are selected
with proper terminal block inputs. Refer to charts on
Pages 5-26 and 5-27.

Units None

Settings ‘‘Remote Pot”

‘‘0-10 Volt”
‘‘4-20 mA”
‘‘MOP”
‘‘Adapter 1”
‘‘Adapter 2”
‘‘Adapter 3”
‘‘Adapter 4”
‘‘Adapter 5”
‘‘Adapter 6”

‘‘Preset 1”
‘‘Preset 2”
‘‘Preset 3”
‘‘Preset 4”
‘‘Preset 5’’
‘‘Preset 6”
‘‘Preset 7”