Appendix b – Rockwell Automation 1305 AC Drive, Firmware 1.01-3.00 User Manual User Manual
Page 145

Appendix B –
Serial Communications
B-7
Table B.4 Parameter Grouping/User Settings (cont.)
Group
Parameter Name
Param-
eter #
Display
Units
Drive Units
Scale Factor ➁
Min
Max
Factory Setting
User‘s
Setting
Minimum Freq
16
Hz
1
0
120
0
Maximum Freq
19
Hz
1
40
400
60
Base Frequency
17
Hz
1
40
400
60
Base Voltage
18
Volts
1
25% of
DRV
Maximum Drive Rated Volts
Maximum DRV
Break Frequency
49
Hz
1
0
120
0
p
Break Voltage
50
Volts
1
0
50% of Max Drive Rated Volts
0
S
et Up
Maximum Voltage
20
Volts
1
25% of
DRV
Maximum Drive Rated Volts
Maximum DRV
ed
S
DC Boost Select
9
Text ➀
1
––
––
No Boost
ance
d
Start Boost
48
Volts
1
0
25% of Max. Drive Rated Volts
0
d
va
n
Run Boost
83
Volts
1
0
25% of Max. Drive Rated Volt
0
Adv
PWM Frequency
45
kHz
10
2.0
8.0
4.0
A
Analog Invert
84
Text ➀
1
––
––
Disabled
4–20 mA Loss Sel
81
Text ➀
1
––
––
Stop/Fault
Stop Select
10
Text ➀
1
––
––
Ramp
DC Hold Time
12
Seconds
1
0
15
0
DC HoId Level
13
Volts
1
0
25% of Max. Drive Rated Volt
0
DB Enable
11
Text ➀
1
––
––
Disabled
Motor Type
41
Text ➀
1
––
––
Induc/Reluc
Compensation
52
Text ➀
1
––
––
No Comp
➀ Refer to Table B.5 on pages B-13, B-14 and B-15 for the numerical equivalent of the text descriptions. ➁ Refer to page B-2.