Data Formats

The data can be configured on board each module as:

engineering units x 1

engineering units x 10

scaled-for-PID

percent of full-scale

raw/proportional data

Filter Frequencies

The module uses a digital filter that provides high frequency noise
rejection for the input signals. The filter is programmable, allowing
you to select from six different filter frequencies for each channel:

10 Hz

50 Hz

60 Hz

250 Hz

500 Hz

1000 Hz

Hardware Features

Channels are wired as differential inputs. A cold junction
compensation (CJC) sensor is attached to the terminal block to enable
accurate readings from each channel. The sensor compensates for
offset voltages introduced into the input signal as a result of the
cold-junction where the thermocouple wires are connected to the
module.

Millivolt Input Type

Range

± 50 mV

-50 to +50 mV

± 100 mV

-100 to +100 mV

Advertising