Repeatability at 25˚c (77˚f), Repeatability at 25°c (77°f) – Rockwell Automation 1762-IT4 Thermocouple/mV Input Module User Manual

Page 79

Advertising
background image

Publication 1762-UM002A-EN-P - July 2002

Specifications A-3

Repeatability at 25°C
(77°F)

(1)

(2)

Specification

Value

Module Error over Full
Temperature Range
(0 to +55°C [+32°F to
+131°F])

See “Accuracy” on page A-4.

CJC Accuracy

±1.3°C (±2.34°F)

Maximum Overload at Input
Terminals

±35V dc continuous

(1)

(1) Maximum current input is limited due to input impedance.

Input Group to Bus Isolation 720V dc for 1 minute (qualification test)

30V ac/30V dc working voltage

Input Channel Configuration via configuration software screen or the user program (by

writing a unique bit pattern into the module’s configuration
file).

Module OK LED

On: module has power, has passed internal diagnostics, and is
communicating over the bus.
Off: Any of the above is not true.

Channel Diagnostics

Over- or under-range and open-circuit by bit reporting

Vendor I.D. Code

1

Product Type Code

10

Product Code

64

(1) Repeatability is the ability of the input module to register the same reading in successive measurements for the

same input signal.

(2) Repeatability at any other temperature in the 0 to 60°C (32 to 140°F) range is the same as long as the

temperature is stable.

Input Type

Repeatability for
10 Hz Filter

Thermocouple J

±0.1°C [±0.18°F]

Thermocouple N (-110°C to +1300°C [-166°F to +2372°F])

±0.1°C [±0.18°F]

Thermocouple N (-210°C to -110°C [-346°F to -166°F])

±0.25°C [±0.45°F]

Thermocouple T (-170°C to +400°C [-274°F to +752°F])

±0 .1°C [±0.18°F]

Thermocouple T (-270°C to -170°C [-454°F to -274°F])

±1.5°C [±2.7°F]

Thermocouple K (-270°C to +1370°C [-454°F to +2498°F])

±0.1°C [±0.18°F]

Thermocouple K (-270°C to -170°C [-454°F to -274°F])

±2.0°C [±3.6°F]

Thermocouple E (-220°C to +1000°C [-364°F to +1832°F])

±0.1°C [±0.18°F]

Thermocouple E (-270°C to -220°C [-454°F to -364°F])

±1.0°C [±1.8°F]

Thermocouples S and R

±0.4°C [±0.72°F]

Thermocouple C

±0.2°C [±0.36°F]

Thermocouple B

±0.7°C [±1.26°F]

±50 mV

±6

µ

V

±100 mV

±6

µ

V

Advertising