Wiring, Wiring -9, Terminal block layout -9 labeling the terminals -9 – Rockwell Automation 1762-IT4 Thermocouple/mV Input Module User Manual

Page 25: Terminal block layout labeling the terminals, Noise prevention

Advertising
background image

Publication 1762-UM002A-EN-P - July 2002

Installation and Wiring 2-9

•

If it is necessary to connect the shield drain wire at the module
end, connect it to earth ground using a panel or DIN rail
mounting screw.

•

Refer to Industrial Automation Wiring and Grounding
Guidelines
, Allen-Bradley publication 1770-4.1, for additional
information.

Noise Prevention

•

Route field wiring away from any other wiring and as far as
possible from sources of electrical noise, such as motors,
transformers, contactors, and ac devices. As a general rule, allow
at least 15.2 cm (6 in.) of separation for every 120V of power.

•

Routing field wiring in a grounded conduit can reduce electrical
noise.

•

If field wiring must cross ac or power cables, ensure that they
cross at right angles.

•

To limit the pickup of electrical noise, keep thermocouple and
millivolt signal wires as far as possible from power and load
lines.

•

If noise persists for a device, try grounding the opposite end of
the cable shield. (You can only ground one end at a time.)

Wiring

Terminal Block Layout

Labeling the Terminals

A write-on label is provided with the module. Mark the identification
of each terminal with permanent ink, and slide the label back into the
door.

IN1 -

IN1 +

IN 0 -

IN 0 +

IN2 -

IN2 +

CJC

CJC

IN3 -

IN3 +

Advertising