Wiring, Wiring -9, Terminal block layout -9 labeling the terminals -9 – Rockwell Automation 1762-IT4 Thermocouple/mV Input Module User Manual

Page 25: Terminal block layout labeling the terminals, Noise prevention

Advertising
background image

Publication 1762-UM002A-EN-P - July 2002

Installation and Wiring 2-9

If it is necessary to connect the shield drain wire at the module
end, connect it to earth ground using a panel or DIN rail
mounting screw.

Refer to Industrial Automation Wiring and Grounding
Guidelines
, Allen-Bradley publication 1770-4.1, for additional
information.

Noise Prevention

Route field wiring away from any other wiring and as far as
possible from sources of electrical noise, such as motors,
transformers, contactors, and ac devices. As a general rule, allow
at least 15.2 cm (6 in.) of separation for every 120V of power.

Routing field wiring in a grounded conduit can reduce electrical
noise.

If field wiring must cross ac or power cables, ensure that they
cross at right angles.

To limit the pickup of electrical noise, keep thermocouple and
millivolt signal wires as far as possible from power and load
lines.

If noise persists for a device, try grounding the opposite end of
the cable shield. (You can only ground one end at a time.)

Wiring

Terminal Block Layout

Labeling the Terminals

A write-on label is provided with the module. Mark the identification
of each terminal with permanent ink, and slide the label back into the
door.

IN1 -

IN1 +

IN 0 -

IN 0 +

IN2 -

IN2 +

CJC

CJC

IN3 -

IN3 +

Advertising