Diagnostics and Troubleshooting 4-3

Power-up Diagnostics

At module power-up, a series of internal diagnostic tests are
performed. If these diagnostic tests are not successfully completed,
the module status LED remains off and a module error is reported to
the controller.

Channel Diagnostics

When an input channel is enabled, the module performs a diagnostic
check to see that the channel has been properly configured. In
addition, the channel is tested on every scan for configuration errors,
over-range and under-range, and open-circuit conditions.

Invalid Channel Configuration Detection

Whenever a channel configuration word is improperly defined, the
module reports an error. See pages 4-4 to 4-6 for a description of
module errors.

Over- or Under-Range Detection

Whenever the data received at the channel word is out of the defined
operating range, an over-range or under-range error is indicated in
input data word 5.

Possible causes of an out-of-range condition include:

•

The temperature is too hot or too cold for the type of
thermocouple being used.

•

The wrong thermocouple is being used for the input type
selected, or for the configuration that was programmed.

•

The input device is faulty.

•

The signal input from the input device is beyond the scaling
range.

If module status
LED is:

Indicated
condition:

Corrective action:

On

Proper Operation

No action required.

Off

Module Fault

Cycle power. If condition persists, replace the
module. Call your local distributor or Rockwell
Automation for assistance.