Publication 1762-UM002A-EN-P - July 2002

Module Data, Status, and Channel Configuration 3-33

Determining Module
Update Time

The module update time is defined as the time required for the
module to sample and convert the input signals of all enabled input
channels and provide the resulting data values to the processor.
Module update time can be calculated by adding the sum of all
enabled channel’s times. The module sequentially samples the
enabled channels in a continuous loop as shown below.

Table 3.4 Effective Resolution vs. Input Filter Selection for Millivolt Inputs

Filter Frequency

±50mV

±100mV

10 Hz

6

µ

V

6

µ

V

50 Hz

9

µ

V

12

µ

V

60 Hz

9

µ

V

12

µ

V

250 Hz

125

µ

V

150

µ

V

500 Hz

250

µ

V

300

µ

V

1 kHz

1000

µ

V

1300

µ

V

TIP

The resolutions provided by the filters apply to the
raw/proportional data format only.

No Thermocouple

Calibration Not Active

Sample

Channel 0

Sample

Channel 1

Sample

Channel 2

Sample

Channel 3

Enabled

Enabled

Enabled

Enabled

TC Enabled

Sample

CJC

Calibration

Active

Perform

Calibration

Channel 3 Disabled

Channel 0 Disabled

Channel 1 Disabled

Channel 2 Disabled