Channel Cut-Off Frequency

The filter cut-off frequency, -3 dB, is the point on the frequency
response curve where frequency components of the input signal are
passed with 3 dB of attenuation. The following table shows cut-off
frequencies for the supported filters.

All input frequency components at or below the cut-off frequency are
passed by the digital filter with less than 3 dB of attenuation. All
frequency components above the cut-off frequency are increasingly
attenuated as shown in the graphs on page 3-13.

Table 3.3 Filter Frequency versus Channel Cut-off Frequency

Filter Frequency

Cut-off Frequency

10 Hz

2.62 Hz

50 Hz

13.1 Hz

60 Hz

15.7 Hz

250 Hz

65.5 Hz

500 Hz

131 Hz

1 kHz

262 Hz