Publication 1762-UM002A-EN-P - July 2002

D-4 Using Thermocouple Junctions

To prevent violation of channel-to-channel isolation:

For multiple exposed junction thermocouples, do not allow the
measuring junctions to make direct contact with electrically
conductive process material.

Preferably use a single exposed junction thermocouple with
multiple ungrounded junction thermocouples.

Consider using all ungrounded junction thermocouples instead
of the exposed junction type.