2-8 Installation and Wiring

Terminal Block

Do not tamper with or remove the CJC sensor on the terminal
block. Removal of the sensor reduces accuracy.

For millivolt sensors, use Belden 8761 shielded, twisted-pair
wire (or equivalent) to ensure proper operation and high
immunity to electrical noise.

For a thermocouple, use the shielded, twisted-pair
thermocouple extension lead wires specified by the
thermocouple manufacturer. Using the incorrect type of
thermocouple extension wire or not following the correct
polarity will cause invalid readings.

To ensures optimum accuracy, limit overall cable impedance by
keeping a cable as short as possible. Locate the module as close
to input devices as the application permits.

Grounding

This product is intended to be mounted to a well-grounded
mounting surface such as a metal panel. Additional grounding
connections from the module’s mounting tabs or DIN rail (if
used) are not required unless the mounting surface cannot be
grounded.

Under normal conditions, the drain wire (shield) should be
connected to the metal mounting panel (earth ground). Keep
shield connection to earth ground as short as possible.

Ground the shield drain wire at one end only. The typical
location is as follows.

For grounded thermocouples or millivolt sensors, this is at the

sensor end.

For insulated/ungrounded thermocouples, this is at the

module end. Contact your sensor manufacturer for additional
details.

ATTENTION

!

The possibility exists that a grounded or exposed
thermocouple can become shorted to a potential
greater than that of the thermocouple itself. Due to
possible shock hazard, take care when wiring
grounded or exposed thermocouples. See Appendix
D, Using Thermocouple Junctions.