Specifications, General specifications, Appendix a – Rockwell Automation 1762-IT4 Thermocouple/mV Input Module User Manual

Page 77: Appendix

Advertising
background image

1

Publication 1762-UM002A-EN-P - July 2002

Appendix

A

Specifications

General Specifications

Specification

Value

Dimensions

90 mm (height) x 87 mm (depth) x 40 mm (width)
height including mounting tabs is 110 mm
3.54 in. (height) x 3.43 in. (depth) x 1.58 in. (width)
height including mounting tabs is 4.33 in.

Approximate Shipping Weight
(with carton)

220g (0.53 lbs.)

Storage Temperature

-40°C to +85°C (-40°F to +185°F)

Operating Temperature

0°C to +55°C (32°F to +131°F)

Operating Humidity

5% to 95% non-condensing

Operating Altitude

2000 meters (6561 feet)

Vibration

Operating: 10 to 500 Hz, 5G, 0.030 in. peak-to-peak
Relay Operation: 2G

Shock

Operating: 30G, 11 ms panel mounted
(20G, 11 ms DIN rail mounted)
Relay Operation: 7.5G panel mounted
(5G DIN rail mounted)
Non-Operating: 40G panel mounted
(30G DIN rail mounted)

Recommended Cable

Belden™ 8761 (shielded) for millivolt inputs
Shielded thermocouple extension wire for the
specific type of thermocouple you are using. Follow
thermocouple manufacturer’s recommendations.

Agency Certification

C-UL certified (under CSA C22.2 No. 142)

UL 508 listed

CE compliant for all applicable directives

C-Tick marked for all applicable acts

Hazardous Environment Class

Class I, Division 2, Hazardous Location, Groups A,
B, C, D

(UL 1604, C-UL under CSA C22.2 No. 213)

Radiated and Conducted Emissions

EN50081-2 Class A

Advertising