Error codes, Error codes -6 – Rockwell Automation 1762-IT4 Thermocouple/mV Input Module User Manual

Page 74

Advertising
background image

Publication 1762-UM002A-EN-P - July 2002

4-6 Diagnostics and Troubleshooting

Error Codes

The table below explains the extended error code.

Table 4.3 Extended Error Codes

Error Type

Hex

Equivalent

(1)

Module

Error
Code

Extended Error

Information

Code

Error Description

Binary

Binary

No Error

X000

000

0 0000 0000

No Error

General Common
Hardware Error

X200

001

0 0000 0000

General hardware error; no additional information

X201

001

0 0000 0001

Power-up reset state

Hardware-Specific
Error

X300

001

1 0000 0000

General hardware error; no additional information

X301

001

1 0000 0001

Microprocessor hardware error

X302

001

1 0000 0010

A/D Converter error

X303

001

1 0000 0011

Calibration error

Module-Specific
Configuration
Error

X400

010

0 0000 0000

General configuration error; no additional information

X401

010

0 0000 0001

Invalid input type selected (channel 0)

X402

010

0 0000 0010

Invalid input type selected (channel 1)

X403

010

0 0000 0011

Invalid input type selected (channel 2)

X404

010

0 0000 0100

Invalid input type selected (channel 3)

X405

010

0 0000 0101

Invalid filter selected (channel 0)

X406

010

0 0000 0110

Invalid filter selected (channel 1)

X407

010

0 0000 0111

Invalid filter selected (channel 2)

X408

010

0 0000 1000

Invalid filter selected (channel 3)

X409

010

0 0000 1001

Invalid format selected (channel 0)

X40A

010

0 0000 1010

Invalid format selected (channel 1)

X40B

010

0 0000 1011

Invalid format selected (channel 2)

X40C

010

0 0000 1100

Invalid format selected (channel 3)

X40D

010

0 0000 1101

An unused bit has been set for channel 0

X40E

010

0 0000 1110

An unused bit has been set for channel 1

X40F

010

0 0000 1111

An unused bit has been set for channel 2

X410

010

0 0001 0000

An unused bit has been set for channel 3

X411

010

0 0001 0001

Invalid module configuration register

(1) X represents the “Don’t Care” digit.

Advertising