Rockwell Automation 1762-IT4 Thermocouple/mV Input Module User Manual

Page 133

Advertising
background image

Publication 1762-UM002A-EN-P - July 2002

Module Configuration Using MicroLogix 1200 and RSLogix 500 E-7

Configuration Using
RSLogix 500 Version 5.2 or
Lower

If you do not have version 5.5 or higher of RSLogix 500, you can still
configure your module, using the Generic Extra Data Configuration
dialog.

The 1762-IT4 uses six 16-bit binary numbers to configure each of its
four channels. To properly configure and enable input channel 1 for
the setting in the table below, add the decimal values given to each of
the six parameters. These decimal values are listed in the
configuration table on page 3-5

.

Enter this value into the Generic Extra Data Config tab.

Table 5.2 1762-IT4 Parameter Decimal Values

Parameter

Setting

Decimal Value

Filter Frequency

250 Hz

3

Open Circuit

Hold Last State

64

Temperature Units

Degrees F

128

Input Type

Thermocouple S

1280

Data Format

Engineering Units x 10

16384

Enable Channel

Enable

-32768

Total -14909