Publication 1762-UM002A-EN-P - July 2002

Installation and Wiring 2-5

Mounting

Minimum Spacing

Maintain spacing from
enclosure walls,
wireways, adjacent
equipment, etc. Allow
50.8 mm (2 in.) of space
on all sides for adequate
ventilation, as shown:

DIN Rail Mounting

The module can be mounted using the following DIN rails:
35 x 7.5 mm (EN 50 022 - 35 x 7.5) or 35 x 15 mm
(EN 50 022 - 35 x 15).

Before mounting the module on a DIN rail, close the DIN rail latch.
Press the DIN rail mounting area of the module against the DIN rail.
The latch will momentarily open and lock into place.

ATTENTION

!

Do not remove protective debris strip until after the
module and all other equipment near the module is
mounted and wiring is complete. Once wiring is
complete and the module is free of debris, carefully
remove protective debris strip. Failure to remove
strip before operating can cause overheating.

TIP

1762 expansion I/O may be mounted horizontally
only.

ATTENTION

!

During panel or DIN rail mounting of all devices, be
sure that all debris (metal chips, wire strands, etc.)
is kept from falling into the module. Debris that falls
into the module could cause damage when power
is applied to the module.

Side

Side

Top

Bottom