Enabling or disabling a channel (bit 15), Selecting data formats (bits 14 through 12) – Rockwell Automation 1762-IT4 Thermocouple/mV Input Module User Manual

Page 36

Advertising
background image

Publication 1762-UM002A-EN-P - July 2002

3-6 Module Data, Status, and Channel Configuration

Enabling or Disabling a Channel (Bit 15)

You can enable or disable each of the four channels individually using
bit 15. The module only scans enabled channels. Enabling a channel
forces it to be recalibrated before it measures input data. Disabling a
channel sets the channel data word to zero.

Selecting Data Formats (Bits 14 through 12)

This selection configures channels 0 through 3 to present analog data
in any of the following formats:

Raw/Proportional Data

Engineering Units x 1

Engineering Units x 10

Scaled for PID

Percent Range

TIP

When a channel is not enabled (0), no input is
provided to the controller by the A/D converter.
This speeds up the response of the active channels,
improving performance.

Table 3.1 Channel Data Word Format

Input
Type

Data Format

Engineering Units x1

Engineering Units x10

Scaled-for-PID

Raw/Proportion

al Data

Percent

Range

°C

°F

°C

°F

J

-2100 to +12000

-3460 to +21920

-210 to +1200

-346 to +2192

0 to +16383

-32767 to +32767

0 to +10000

K

-2700 to +13700

-4540 to +24980

-270 to +1370

-454 to +2498

0 to +16383

-32767 to +32767

0 to +10000

T

-2700 to +4000

-4540 to +7520

-270 to +400

-454 to +752

0 to +16383

-32767 to +32767

0 to +10000

E

-2700 to +10000

-4540 to +18320

-270 to +1000

-454 to +1832

0 to +16383

-32767 to +32767

0 to +10000

R

0 to +17680

+320 to 32140

0 to +1768

+32 to 3214

0 to +16383

-32767 to +32767

0 to +10000

S

0 to +17680

+320 to 32140

0 to +1768

+32 to 3214

0 to +16383

-32767 to +32767

0 to +10000

B

+3000 to 18200

+5720 to 32767

(1)

+300 to 1820

+572 to 3308

0 to +16383

-32767 to +32767

0 to +10000

N

-2100 to +13000

-3460 to +23720

-210 to +1300 -346 to +2372

0 to +16383

-32767 to +32767

0 to +10000

C

0 to +23150

+320 to 32767

(1)

0 to +2315

+32 to 4199

0 to +16383

-32767 to +32767

0 to +10000

±50 mV

-5000 to +5000

(2)

-500 to +500

(2)

0 to +16383

-32767 to +32767

0 to +10000

±100 mV -10000 to 10000

(2)

-1000 to 1000

(2)

0 to +16383

-32767 to +32767

0 to +10000

(1) Type B and C thermocouples cannot be represented in engineering units x1 (°F) above 3276.7 °F; therefore, it will be treated as an over-range error.

(2) When millivolts are selected, the temperature setting is ignored. Analog input date is the same for °C or °F selection.