Calculating module update time -35, Calculating module update time – Rockwell Automation 1762-IT4 Thermocouple/mV Input Module User Manual

Page 65

Advertising
background image

Publication 1762-UM002A-EN-P - July 2002

Module Data, Status, and Channel Configuration 3-35

separate ADC self-calibration and offset calibration cycles only if their
filter configurations are different than those of previously calibrated
channels.

Following all input channel calibration cycles, the CJC sensor channel
receives a separate ADC self-calibration cycle. The time added to this
cycle is determined by the filter setting for the CJC, which is set to the
lowest filter setting of any input configured as a thermocouple. If no
enabled input channel is configured for a thermocouple, no CJC
calibration cycle occurs. See Table 3.6 below for channel and CJC
sensor ADC self-calibration times as well as channel offset calibration
times.

Calculating Module Update Time

To determine the module update time, add the individual channel
update times for each enabled channel and the CJC update time if any
of the channels are enabled as thermocouple inputs.

Table 3.6 Calibration Time

Type of Calibration

10 Hz

50 Hz

60 Hz

250 Hz

500 Hz

1 kHz

ADC self-calibration
(Channels 0 through 3)

603

123

103

27

15

9

Offset calibration
(Channels 0 through 3)

303

63

53

15

9

6

ADC self-calibration
(CJC sensor)

603

123

103

27

15

9

EXAMPLE

1. Two Channels Enabled for Millivolt Inputs

Channel 0 Input: ±50 mV with 60 Hz filter
Channel 1 Input: ±50 mV with 500 Hz filter

From Table 3.5, Channel Update Time, on page 3-34:

Module Update Time
= Ch 0 Update Time + Ch 1 Update Time
= 53 ms + 9 ms
= 62 ms

Advertising