Installing the

Thermocouple/Millivolt Input

Module

This chapter gives you information on:

calculating the chassis power requirement

choosing the module’s location in the I/O chassis

keying a chassis slot for your module

wiring the input module’s field wiring arm

installing the input module

Before installing your input module in the I/O chassis you must:

Action required:

Refer to:

Calculate the power requirements of all modules in each chassis.

Calculate Power Requirements

Determine where to place the module in the I/O chassis.

Module Location in the I/O Chassis

Key the backplane connector in the I/O chassis.

Module Keying

Make connections to the wiring arm.

Connecting Wiring and Grounding

The thermocouple/mV input module is sensitive to electrostatic
discharge.

!

ATTENTION: Electrostatic discharge can damage
integrated circuits or semiconductors if you touch
backplane connector pins. Follow these guidelines
when you handle the module:

Touch a grounded object to discharge static potential

Wear an approved wrist-strap grounding device

Do not touch the backplane connector or
connector pins

Do not touch circuit components inside the module

If available, use a static-safe work station

When not in use, keep the module in its
static-shield bag

Chapter Objectives

Before YouInstall Your

Input Module

Prevent Electrostatic

Discharge